• Product Details
  • Additional Information
  • Inquiry

Product Description

Outdoor Switch-disconnector(IACM)LBS-24~36/400-50 

1. Overview

 LBS-12~36/400-50A (IACM -12~36/400-50A) is a new type of load switch designed and manufactured with advanced technology. This load switch is composed of an isolation gate knife, arc rod, etc. When the current is interrupted, the arc rod stores energy and moves quickly to open the circuit, lengthening the arc and cooling it with air extinguish it. The speed of the arc contact movement is not affected by the speed of manual operation, and it has the principle of rapid arc extinguishing after reaching safe break, with the advantages of simple structure, less maintenance work, strong arc extinguishing ability, high insulation level of the break, and high reliability, reaching the level of similar products at home and abroad. The switch can be used for radial, ring network lines and transformer circuits (used with high-voltage current limiting fuses short-circuit protection) or for current-free isolation.

This series of switches is designed and manufactured in accordance with the following standards: IEC 60265-1 High-Voltage Switches - Part 1: Switches for Rated Voltages Above 1 kV and Less Than 52 kV 

IEC 62271-1 High-voltage switchgear and controlgear – Part 1: Common specific ations for alternating current switchgear and controlgear 

IEC 62271-103 HIGH-VOLTAGE SWITCHGEAR AND CONTROLGEAR - PART 103: SWITCHES FOR RATED VOLTAGES ABOVE 1 KV UP TO AND INCLUDING 52 KV 

2. Environmental Conditions for Use 

Ambient air temperature for use: ≤40 ℃/-30 ℃, with a daily temperature difference not exceeding 32K; Altitude:≤2000m Air pollution level: Grade IV to GB5585 Article Maximum wind speed: Wind pressure not exceeding 700Mpa Seismic capacity: Earthquake intensity not 8 degrees Load: Ice thickness not exceeding 10mm

DesignsequencenumberPlaceofuse(out)AirinsulationLoadswitch Companycode


3.Technical Parameters

 

NO.

ltem

Unit

Data

1

Rated voltage

KV

12

17.5

24

36

2

Rated current

A

200/400/630/1250

3

Rated active load breaking current

A

50

50

50

50

4

Rated No-load transformer breaking current

A

2.5

2.5

2.5

2.5

5

Rated No-load line breaking capacity

A

10

10

10

10

 

6

 

1min power frequency withstand voltage

phase to phase, to earth

KV

42

45

55

95

across open contacts

KV

48

55

69

105

 

 

7

 

Lightning impulse withstand voltage

phase to phase, to earth

KV

75

95

125

170

across open contacts

KV

85

105

145

195

8

Rated short-time withstand curent

KA

12.5

12.5

12.5

12.5

9

Rated short-circuit duration

S

1

1

1

1

10

Rated peak withstand current

KA

31.5

31.5

31.5

31.5

11

 

Mechanical life

Times

2000

2000

2000

2000

12

Manual operating torque

Nm

≤200

≤200

≤200

≤200

13

Contact opening distance

mm

>500

>60

>800

>1030

14

The position of the contact just closed is skewed

mm

>2/3

>2/3

>2/3

>2/3

15

Contact pressure

N

200

200

200

200

16

Three phase closing at different stages

mm

<3

<3

<3

<3

17

Distance between charged bodies and relative ground

mm

>160

>200

>260

>330

18

Main loop resistance

uΩ

≤150

≤150

≤150

≤150


负荷开关2(1)