Advantages:
● Integrated High-Creepage Pole Design: Optimized electric field distribution with superior insulation performance;
● Vacuum Interrupter + Knife-Type Disconnector + Grounding Switch: Reliable operation and extended lifespan;
● High Protection Level Enclosure with Anti-Condensation Design: Suitable for harsh environments such as high humidity and pollution;
● European Standardized Interfaces: Easy expansion and cabinet assembly for main busbar and cable terminations, ensuring safety and stability;
● Specialized Epoxy Resin Material:
a. High mechanical strength;
b. Crack resistance, thermal stability, high thermal conductivity, and aging resistance;
c. Glass transition temperature >110°C, maintaining insulation performance under high temperatures;
● Human-Machine Interface Optimization: Intuitive and user-friendly controls, reliable mechanical interlocks, and visible isolation gap with LED indication for enhanced safety;
● Motorized Disconnector Operation: Supports on-demand motorized operation, seamlessly integrating with distribution automation systems;
● Maintenance-Friendly Design: Front-access panel for quick component replacement and circuit inspection, minimizing downtime.
| Item | Unit | Circuit Breaker Unit | Load Switch Unit | Switch-fuse Combinations Unit | ||
| 1 | Rated Voltage | kV | 12 | 12 | 12 | |
| 2 | Rated Frequency | Hz | 50 | 50 | 50 | |
| 3 | Rated Current | A | 630/1250 | 630/1250 | Dependent on Fuse Current Rating | |
| 4 | Rated Insulation Level | Power Frequency Withstand Voltage(Phase-to-Phase/Phase-to-Ground) | kV | 42 | 42 | 42 |
| 5 | Power Frequency Withstand Voltage(Vacuum Interrupter/ lsolation Gap) | 48 | 48 | 48 | ||
| 6 | Power Frequency Withstand Voltage(Control and Auxliary Circuits) | 2 | 2 | 2 | ||
| 7 | Lightning Impulse Withstand Voltage(Phase-to-Phase/Phase-to-Ground) | 75 | 75 | 75 | ||
| 8 | Lightning Impulse Withstand Valtage(Vacuum lnterrupter / lsolation Gap) | 85 | 85 | 85 | ||
| 9 | Rated Short-Time Withstand Current | kA | 20(25)/4S | 20(25)/4S | —— | |
| 10 | Rated Peak Withstand Current | kA | 50(63) | 50(63) | —— | |
| 11 | Rated Short-Circuit Making Current | kA | 50(63) | 50(63) | Limited by High-Voltage Fuse | |
| 12 | Rated Short-Circuit Breaking Curent | kA | 20(25) | 20(25) | Limited by High-Voltage Fuse | |
| 13 | Rated Transfer Current | A | —— | —— | 1700 | |
| 14 | Rated Active Load Breaking Cument | A | —— | —— | —— | |
| 15 | Rated Closed-Loop Breaking Current | A | 630 | 630 | —— | |
| 16 | Internal Arc Fault Test (AFLR Class) | kA/S | 20(25)/0.5S | 20(25)/0.5S | —— | |
| 17 | Partial Discharge (at 1.2Ur) | PC | ≤10 | ≤10 | —— | |
| 18 | Ingress Protection (IP) Rating (Cabinet) | IP4X | IP4X | IP4X | ||
| 19 | Main Circuit Resistance | μΩ | ≤120 | ≤120 | —— | |
| 20 | Mechanical Endurance | Circuit Breaker / Load Switch | Times | 10000 | 10000 | 10000 |
| 21 | Disconnector/Grounding Switch | 3000 | 3000 | 3000 | ||


Copyright © 2021 By JGGY Electrical.com